Power Distribution Units running on Powertek firmware ...
Critical severity
Unreviewed
Published
Jun 14, 2022
to the GitHub Advisory Database
•
Updated Jan 27, 2023
Description
Published by the National Vulnerability Database
Jun 13, 2022
Published to the GitHub Advisory Database
Jun 14, 2022
Last updated
Jan 27, 2023
Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.