[ENHANCEMENT]: Improved Heat meter #100
Comments
Hello, small update: I found in the spare parts list that the fan motor has 60W as power rating. I have now integrated the whole thing via Home Assistant to have a more accurate representation here. Unfortunately, I have no experience how the whole thing would have to be implemented in NodeRed - so I have helped me first about Home Assistant.
|
First off, thank you for the propper detailed request. This is how I like things to be handed . Clear. Now the content. You split the contributors for the energye nicely apart. I can create the function, and put the code in here. Thanks again for the effort !! |
:D this item is not done yet. |
Hello,
the integrated heat meter of the Heisha/Jeisha is bad - it is always rounded down to a whole 200 watts ... not everyone wants to install an external counter.
But I think with the existing data, a much better one can be calculated itself:
Real power consumption:
Compressor consumption + fan consumption + pump consumption:
Compressor: (for the single-phase models).
Amps from compressor mulitplied with 230V = gives an accurate watts for the compressor. Amps are much more accurate with a decimal place.
Circulation Pump:
The circulating pump needs 39W to 109W depending on the power.
Simply link with the hex number and assume a value.
Fan:
Here there is no indication what the min and max value would be - maybe someone has an idea?
Real heat quantity:
Volume flow per hour in liters x 1 (density) x 1.16 (specific heat capacity) x (Outlet - Inlet)K (Difference between these Temperatures)
Additional:
When defrost mode is active, the amount of heat must be subtracted.
Currently the heat pump calculates the defrost with a COP of 7-10 which distorts the COP.
I think it would give a much more accurate statement about the efficiency of the heat pump if the calculations are integrated. Of course, this is not yet an accurate measurement, but it would be a significant improvement over the 200-watt steps that currently happen.