Original file line number Diff line number Diff line change
@@ -0,0 +1,238 @@
within Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints;
block CondensationControl
"Sequence to calculate setpoint limits for condensation control in non-condesing boilers"

parameter Boolean have_priOnl = false
"True: Primary-only plant; False: Primary-secondary plant";

parameter Boolean have_varPriPum = true
"True: Variable speed pumps in primary loop; False: Constant speed pumps in primary loop"
annotation(Evaluate=true,Dialog(enable=(not have_priOnl)));

parameter Integer nSta=5
"Number of stages";

parameter Real TRetSet(
final unit="K",
final displayUnit="K",
final quantity="ThermodynamicTemperature") = 60
"Minimum hot water return temperature for optimal non-condensing boiler performance";

parameter Real TRetMinAll(
final unit="K",
final displayUnit="K",
final quantity="ThermodynamicTemperature") = 57.2
"Minimum allowed hot water return temperature for non-condensing boiler";

parameter Real minSecPumSpe(
final unit="1",
final displayUnit="1",
final min=0,
final max=1) = 0
"Minimum secondary pump speed";

parameter Real minPriPumSpeSta[nSta](
final unit="1",
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Please use final unit=fill("1", nSta) and equivalent edits to all attributes of a vectorized parameter. For now we also use for any such parameters an annotation such as this one: annotation (Evaluate=true);. This annotation will become obsolete once this issue has been resolved and we will do a refactor to remove it then.

final displayUnit="1",
final min=0,
final max=1) = {0,0,0,0,0}
"Vector of minimum primary pump speed for each stage";

Buildings.Controls.OBC.CDL.Interfaces.IntegerInput uCurSta
"Current stage"
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Is there a reason not to use uSta?

annotation (Placement(transformation(extent={{-140,-20},{-100,20}}),
iconTransformation(extent={{-140,-20},{-100,20}})));

Buildings.Controls.OBC.CDL.Interfaces.IntegerInput uStaTyp[nSta]
"Stage type vector"
annotation (Placement(transformation(extent={{-140,-90},{-100,-50}}),
iconTransformation(extent={{-140,-80},{-100,-40}})));

Buildings.Controls.OBC.CDL.Interfaces.RealInput THotWatRet(
final unit="K",
final displayUnit="K",
final quantity="ThermodynamicTemperature")
"Measured hot water return temperature"
annotation (Placement(transformation(extent={{-140,50},{-100,90}}),
iconTransformation(extent={{-140,40},{-100,80}})));

Buildings.Controls.OBC.CDL.Interfaces.RealOutput yMinBypValPos(
final unit="1",
final displayUnit="1",
final min=0,
final max=1) if have_priOnl
"Minimum allowed setpoint of bypass valve position"
annotation (Placement(transformation(extent={{100,30},{140,70}}),
iconTransformation(extent={{100,40},{140,80}})));

Buildings.Controls.OBC.CDL.Interfaces.RealOutput yMinPriPumSpe(
final unit="1",
final displayUnit="1",
final min=0,
final max=1) if (have_varPriPum and not have_priOnl)
"Minimum allowed primary pump speed"
annotation (Placement(transformation(extent={{100,-20},{140,20}}),
iconTransformation(extent={{100,-20},{140,20}})));

Buildings.Controls.OBC.CDL.Interfaces.RealOutput yMaxSecPumSpe(
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Based on the conventions please place Min or Max always as a suffix (unless you have a suffix with a leading underscore to use after it, for example _flow for any flow variables.). Here for example you should name the output ySecPumSpeMax.

final unit="1",
final displayUnit="1",
final min=0,
final max=1) if not have_priOnl
"Maximum allowed secondary pump speed"
annotation (Placement(transformation(extent={{100,-70},{140,-30}}),
iconTransformation(extent={{100,-80},{140,-40}})));

protected
Buildings.Controls.OBC.CDL.Logical.Switch swi
"Pass 0 regulation signal if stage type is not non-condensing"
annotation (Placement(transformation(extent={{-50,40},{-30,60}})));

Buildings.Controls.OBC.CDL.Continuous.Sources.Constant con(
final k=0)
"Zero source"
annotation (Placement(transformation(extent={{-90,20},{-70,40}})));

Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences.ProportionalRegulator proReg(
final TRetSet=TRetSet,
final TRetMinAll=TRetMinAll)
"Proportional regulator"
annotation (Placement(transformation(extent={{-90,60},{-70,80}})));

Buildings.Controls.OBC.CDL.Routing.RealExtractor extIndSig(
final nin=nSta)
"Identify stage type for current stage"
annotation (Placement(transformation(extent={{-50,-80},{-30,-60}})));

Buildings.Controls.OBC.CDL.Conversions.IntegerToReal intToRea[nSta]
"Integer to Real conversion"
annotation (Placement(transformation(extent={{-90,-80},{-70,-60}})));

Buildings.Controls.OBC.CDL.Continuous.GreaterThreshold greThr(
final threshold=Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.Types.BoilerTypes.condensingBoiler)
"Identify if current stage is condensing type or non-condensing type"
annotation (Placement(transformation(extent={{-10,-80},{10,-60}})));

Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences.PumpSpeedLimits pumSpeLim(
final have_varPriPum=have_varPriPum,
final nSta=nSta,
final minSecPumSpe=minSecPumSpe,
final minPriPumSpeSta=minPriPumSpeSta) if not have_priOnl
"Block to calculate pump speed limits"
annotation (Placement(transformation(extent={{-10,-10},{10,10}})));

equation
connect(THotWatRet, proReg.THotWatRet)
annotation (Line(points={{-120,70},{-92,70}},
color={0,0,127}));

connect(yMinBypValPos, yMinBypValPos)
annotation (Line(points={{120,50},{120,50}}, color={0,0,127}));

connect(uStaTyp, intToRea.u)
annotation (Line(points={{-120,-70},{-92,-70}},
color={255,127,0}));

connect(intToRea.y, extIndSig.u)
annotation (Line(points={{-68,-70},{-52,-70}},
color={0,0,127}));

connect(uCurSta, extIndSig.index) annotation (Line(points={{-120,0},{-60,0},{-60,
-90},{-40,-90},{-40,-82}},
color={255,127,0}));

connect(extIndSig.y, greThr.u)
annotation (Line(points={{-28,-70},{-12,-70}},
color={0,0,127}));

connect(proReg.yRegSig, swi.u1) annotation (Line(points={{-68,70},{-60,70},{-60,
58},{-52,58}}, color={0,0,127}));
connect(greThr.y, swi.u2) annotation (Line(points={{12,-70},{20,-70},{20,-50},
{-56,-50},{-56,50},{-52,50}}, color={255,0,255}));
connect(swi.y, yMinBypValPos) annotation (Line(points={{-28,50},{120,50}},
color={0,0,127}));
connect(con.y, swi.u3) annotation (Line(points={{-68,30},{-60,30},{-60,42},{-52,
42}}, color={0,0,127}));
connect(swi.y, pumSpeLim.uRegSig) annotation (Line(points={{-28,50},{-20,50},{
-20,-5},{-12,-5}}, color={0,0,127}));
connect(uCurSta, pumSpeLim.uCurSta) annotation (Line(points={{-120,0},{-60,0},
{-60,5},{-12,5}}, color={255,127,0}));
connect(pumSpeLim.yMinPriPumSpe, yMinPriPumSpe)
annotation (Line(points={{12,5},{30,5},{30,0},{120,0}},color={0,0,127}));
connect(pumSpeLim.yMaxSecPumSpe, yMaxSecPumSpe) annotation (Line(points={{12,-5},
{30,-5},{30,-50},{120,-50}}, color={0,0,127}));
annotation (defaultComponentName=
"conSet",
Icon(graphics={
Rectangle(
extent={{-100,100},{100,-100}},
lineColor={0,0,0},
fillColor={255,255,255},
fillPattern=FillPattern.Solid,
lineThickness=0.1),
Rectangle(
extent={{-100,100},{100,-100}},
lineColor={28,108,200},
fillColor={255,255,255},
fillPattern=FillPattern.Solid,
lineThickness=5,
borderPattern=BorderPattern.Raised),
Text(
extent={{-120,146},{100,108}},
lineColor={0,0,255},
textString="%name"),
Ellipse(
extent={{-80,80},{80,-80}},
lineColor={28,108,200},
fillColor={170,255,213},
fillPattern=FillPattern.Solid)},
coordinateSystem(
preserveAspectRatio=false,
extent={{-100,-100},{100,100}})),
Diagram(
coordinateSystem(preserveAspectRatio=false,
extent={{-100,-100},{100,100}})),
Documentation(
info="<html>
<p>
Block that generates condensation control setpoints according to ASHRAE RP-1711,
March, 2020 draft, section 5.3.5.
</p>
<p>
The sequence calculates the condensation control setpoints for minimum bypass
valve position <code>yMinBypValPos</code>, minimum primary pump speed <code>yMinPriPumSpe</code>
and maximum secondary pump speed <code>yMaxSecPumSpe</code> using the following calculations:
<ol>
<li>
Block <code>proReg</code> implemented in the class
<a href=\"modelica://Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences.ProportionalRegulator\">
Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences.ProportionalRegulator</a>
uses the measured hot water return temperature <code>THotWatRet</code> to generate a regulation signal with P-only control loop.
</li>
<li>
The regulation signal is used as is for <code>yMinBypValPos</code>.
</li>
<li>
The regulation signal is used by block <code>pumSpeLim</code> implemented in the class
<a href=\"modelica://Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences.PumpSpeedLimits\">
Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences.PumpSpeedLimits</a>
to generate the pump speed limits <code>yMinPriPumSpe</code> and <code>yMaxSecPumSpe</code>.
</li>
</ol>
<p align=\"center\">
<img alt=\"Validation plot for PlantEnable\"
src=\"modelica://Buildings/Resources/Images/Controls/OBC/ASHRAE/PrimarySystem/BoilerPlant/SetPoints/CondensationControl.png\"/>
<br/>
Validation plot generated from model <a href=\"modelica://Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Validation.CondensationControl\">
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Per Michael's guidance please remove the validation plots from the blocks themselves. This will be needed for the sequence export purposes.

Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Validation.CondensationControl</a>.
</p>
</html>",
revisions="<html>
<ul>
<li>
May 18, 2020, by Karthik Devaprasad:<br/>
First implementation.
</li>
</ul>
</html>"));
end CondensationControl;
Original file line number Diff line number Diff line change
@@ -0,0 +1,128 @@
within Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences;
block ProportionalRegulator
"Sequence to calculate regulation signal with measured return temperature as input"

parameter Real TRetSet(
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Are you usually using THotWat... It might be useful to have it fully spelled out here as well.

Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

The reason is that it makes the instance name better searchable in any text editor.

final unit="K",
final displayUnit="K",
final quantity="ThermodynamicTemperature") = 60
"Minimum hot water return temperature for optimal non-condensing boiler performance";

parameter Real TRetMinAll(
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Min at the end.

final unit="K",
final displayUnit="K",
final quantity="ThermodynamicTemperature") = 57.2
"Minimum allowed hot water return temperature for non-condensing boiler";

Buildings.Controls.OBC.CDL.Interfaces.RealInput THotWatRet(
final unit="K",
final displayUnit="K",
final quantity="ThermodynamicTemperature")
"Measured hot water return temperature"
annotation (Placement(transformation(extent={{-140,-20},{-100,20}}),
iconTransformation(extent={{-140,-20},{-100,20}})));

Buildings.Controls.OBC.CDL.Interfaces.RealOutput yRegSig(
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Could this be only y, as the model name indicates it is a regulator signal?

final unit="1",
final displayUnit="1",
final min=0,
final max=1)
"Regulation signal from P-only loop for condensation control"
annotation (Placement(transformation(extent={{100,-20},{140,20}}),
iconTransformation(extent={{100,-20},{140,20}})));

protected
Buildings.Controls.OBC.CDL.Continuous.AddParameter addPar(
final p=TRetSet,
final k=-1)
"Compare hot water return temperature and minimum return temperature"
annotation (Placement(transformation(extent={{-60,-10},{-40,10}})));

Buildings.Controls.OBC.CDL.Continuous.Limiter lim(
final uMax=TRetSet - TRetMinAll,
Copy link
Contributor

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

This is not permitted in CDL. You could use min/max and have it be an input.

final uMin=0)
"Limit input for calculating control signal"
annotation (Placement(transformation(extent={{-10,-10},{10,10}})));

Buildings.Controls.OBC.CDL.Continuous.Gain gai(
final k=1/(TRetSet - TRetMinAll))
"Calculate control signal"
annotation (Placement(transformation(extent={{40,-10},{60,10}})));

equation
connect(addPar.u, THotWatRet)
annotation (Line(points={{-62,0},{-120,0}}, color={0,0,127}));

connect(lim.u, addPar.y)
annotation (Line(points={{-12,0},{-38,0}}, color={0,0,127}));

connect(lim.y, gai.u)
annotation (Line(points={{12,0},{38,0}}, color={0,0,127}));

connect(gai.y, yRegSig)
annotation (Line(points={{62,0},{120,0}}, color={0,0,127}));

annotation (defaultComponentName=
"proReg",
Icon(graphics={
Rectangle(
extent={{-100,100},{100,-100}},
lineColor={0,0,0},
fillColor={255,255,255},
fillPattern=FillPattern.Solid,
lineThickness=0.1),
Rectangle(
extent={{-100,100},{100,-100}},
lineColor={28,108,200},
fillColor={255,255,255},
fillPattern=FillPattern.Solid,
lineThickness=5,
borderPattern=BorderPattern.Raised),
Text(
extent={{-120,146},{100,108}},
lineColor={0,0,255},
textString="%name"),
Ellipse(
extent={{-80,80},{80,-80}},
lineColor={28,108,200},
fillColor={170,255,213},
fillPattern=FillPattern.Solid)},
coordinateSystem(
preserveAspectRatio=false,
extent={{-100,-100},{100,100}})),
Diagram(
coordinateSystem(preserveAspectRatio=false,
extent={{-100,-100},{100,100}})),
Documentation(
info="<html>
<p>
Block that generates proportional regulation signal for condensation control
in non-condensing boilers according to RP-1711, March, 2020 draft, section
5.3.5.
</p>
<p>
The minimum bypass valve position <code>yProReg</code> is calculated
as follows:
<li>
The measured hot-water return temperature <code>THotWatRet</code> is compared
to the minimum hot water return temperature for optimal operation <code>TRetSet</code>,
with the output <code>yProReg</code> varying linearly from 0% at
<code>TRetSet</code> to 100% at <code>TRetMinAll</code>.
</li>
<p align=\"center\">
<img alt=\"Validation plot for ValvePosition\"
src=\"modelica://Buildings/Resources/Images/Controls/OBC/ASHRAE/PrimarySystem/BoilerPlant/SetPoints/Subsequences/ProportionalRegulator.png\"/>
<br/>
Validation plot generated from model <a href=\"modelica://Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences.Validation.ProportionalRegulator\">
Buildings.Controls.OBC.ASHRAE.PrimarySystem.BoilerPlant.SetPoints.Subsequences.Validation.ProportionalRegulator</a>.
</p>
</html>",
revisions="<html>
<ul>
<li>
July 21, 2020, by Karthik Devaprasad:<br/>
First implementation.
</li>
</ul>
</html>"));
end ProportionalRegulator;