Startup class assignment #26

Open
emgre opened this issue Nov 12, 2020 · 2 comments
Open

Startup class assignment #26

emgre opened this issue Nov 12, 2020 · 2 comments
Labels
enhancement New feature or request master Master issue

Comments

@emgre
Copy link
Contributor

emgre commented Nov 12, 2020

Optionally, specify the class assignements at startup (whenever a restart is detected).

@emgre emgre added enhancement New feature or request master Master issue labels Nov 12, 2020
@jadamcrain
Copy link
Member

We need to research this feature a bit. It's not clear to me if this is something that outstation is required to persist or not. This impacts whether you want this to be a startup behavior or something adhoc.

@emgre
Copy link
Contributor Author

emgre commented Nov 30, 2020

IEEE 1815-2012 p. 63:

Outstation devices that are able to store the most recent class assignments in non-volatile memory may use
those assignments after a device restart; otherwise, devices shall revert to their default class assignments.

Persistence is not mandatory.